I. Flow Measurement Instruments

1. PROMAG50 Electromagnetic Flowmeter

Application: Conductive liquid flow measurement

Pre-power Check:

  • Sensor full pipe, horizontal or vertical installation (flow upward)
  • Straight pipe runs: upstream 5D, downstream 3D
  • Lining intact, electrodes clean
  • Separate reliable grounding, resistance <10Ω

Quick Setup: Press E → QUICK SETUP → Password 50

  • Unit: m³/h
  • Range: 4mA=0, 20mA=full scale
  • Damping: 2-5s
  • Pipe diameter DN: per nameplate
  • Low flow cutoff: 0.5%-1% of range
  • Empty pipe detection: ON

Press +/- together for 3s to return

Zero Calibration: Full pipe, static, no flow → Menu → Calibration → Zero Adjust → Press E → Wait 10s → Zero OK (Normal: ±0.01 m³/h)

Current Check: 0%=4mA, 50%=12mA, 100%=20mA

2. PROMASS 80F Coriolis Flowmeter

Application: High-precision mass flow, density, temperature

Pre-power Check: Full pipe, no bubbles, no vibration; avoid strong magnetic fields and >200°C; flange seals intact; housing grounded

Basic Setup:

  • Setup → Unit → Mass flow: kg/h
  • Range: 4mA=0, 20mA=full scale
  • Damping: 2-5s
  • Fluid: Liquid/Gas
  • Measuring mode: Standard/Symmetry

Zero Calibration: Full pipe, no flow, static → Menu → Calibration → Zero adjust → Press E → Wait 30s → Complete. NEVER calibrate with empty pipe!

Empty Pipe Detection: Menu → Setup → Empty pipe → ON, threshold default 5%

3. 72F Vortex Flowmeter

Application: Steam, gas, liquid flow measurement

Installation: Upstream ≥10D, downstream ≥5D straight runs; arrow matches flow direction; horizontal pipes level, vertical pipes bottom-to-top; away from pumps/compressors

Wiring: 24V DC, 4-20mA+HART

Quick Commissioning: Long press E 3s → Basic menu

  • Set Tag and medium type (Steam/Gas/Liquid)
  • Unit: Steam=kg/h, Gas=Nm³/h, Liquid=m³/h
  • Enter Range span
  • Select Diameter (e.g., DN50)

Mass Flow Calculation:

  • Temp: Select Internal (built-in sensor)
  • Pressure: External if transmitter connected, else fixed working pressure

Zero Calibration: Full pipe, no flow, temp stable → Menu → Cal → Zero Cal → Wait 60s → OK. Output → LFC set 2%-5% low flow cutoff

Errors: A001=Vibration (reinforce piping); A002=Low flow (check cutoff or valve)

4. DTT31 Thermal Mass Flowmeter

Application: Cooling water, lubricating oil low flow monitoring

Installation: Full pipe; 5D upstream straight run; sensor fully immersed, tip at pipe center, insertion ≥10mm; horizontal=side mount, vertical=bottom-to-top

Display: White=normal, Red=alarm

Wiring: 24V DC, output 4-20mA + 1-2 switch outputs

Commissioning: Long press E 3s → Basic menu → Set unit (kg/h or m³/h), range, output mode

Two-Point Calibration:

  • Learn Low (0%): Stop pump, zero flow → Press E → 30s → OK
  • Learn High (100%): Max stable flow → Press E → 30s → OK
  • Select YES when prompted SAVE?

Faults: W432=Unstable calibration retry; Flow drift → Set Temp Comp ON

II. Level & Pressure Instruments

5. FMR245 Radar Level Transmitter

Application: Non-contact liquid, slurry, solids (26GHz)

Installation: ≥300mm from tank wall, avoid inlets/agitators; antenna perpendicular to surface; nozzle height ≤150mm, ID ≥100mm

Quick Setup: Long press E 3s → Basic Setup

  • Language: Select
  • Tank Shape: Vertical/Horizontal/Sphere
  • Medium: Liquid/Solid
  • Empty Cal (0%): Distance D from flange to lowest level
  • Full Cal (100%): Distance L from flange to highest level

Echo Optimization: Menu → Envelope → Auto Learn → Auto scan 30s (filters interference)

안전: Safety menu set SD safety distance (e.g., 0.2m)

Test: Output → Test → Manual output 4mA/12mA/20mA to verify DCS

6. FMU23X Ultrasonic Level Transmitter

Application: Standard liquid and solids level

Installation: Probe parallel to surface; ≥30cm from tank wall; off-center from tank top; avoid inlets/obstacles

Factory Reset: Press V+H together → Display V9H5 → Change to 333 → Press H

구경 측정:

  • Empty: V0H1 → Enter sensor to zero distance → Press H
  • Full: V0H2 → Enter zero to full scale distance → Press H

Fault Check: Err displayed → Enter V9H0 for error code

7. FMM50 Plumb Bob Level Sensor

Application: Large solids silos mechanical measurement

Commissioning:

  • Basic setup → Empty: Flange to reference zero distance
  • Block distance: Flange to weight end safety distance
  • Full: 20mA corresponding max level distance
  • Mode: Periodical (cyclic measurement)
  • Time interval: Set cycle
  • Current output → Standard → 4-20mA
  • Linearization → Level DU → Linear → Unit m

Press +/- together to return

8. PMP71 Pressure Transmitter

Application: High-precision pressure measurement

Local Setup: Long press E 2s → Setup

  • Unit: bar/MPa/kPa
  • Measuring range: LRV lower, URV upper
  • Damping: 2-5s

Position Zero: Zero pressure, drain valve open, membrane vented → Setup → Pos. zero adjust → Confirm → Adjustment OK (Output 4.000mA)

HART Communicator:

  • Connect across signal lines → Auto-detect PMP71
  • Verify Tag and range
  • Device Setup → Calibration → Zero Trim
  • With pressure source: 100% pressure → Span Trim enter standard
  • Check 50% point: Should be 12.000mA (±0.02mA)

III. Water Quality Analyzers

9. COM223/COM253 Dissolved Oxygen

Application: Wastewater and industrial water monitoring

Air Calibration: Install membrane with electrolyte → Expose to air (avoid sun, 20-25°C) → Connect transmitter → Press CAL → Password 22 → Air cal → E confirm → Value drops 600 to 0 → No error = complete

Normal Range:

  • Altitude mode: 6.00-11.20mg/l or 85%-157%SAT
  • Salinity mode: 9.20-9.30mg/l or 102%SAT

Settings:

  • Unit: E → Password 22 → Setup1 → Unit → mg/L
  • Current output: E → Password 22 → — → Output → 4-20mA → Enter concentration values

Maintenance: Weekly water rinse; Industrial wastewater (H₂S, ammonia, etc.) requires more frequent cleaning/membrane replacement

10. CPM223/CPM253 ORP Analyzer

Application: Oxidation-reduction potential

Startup Setup: (May default to pH, change immediately)

  • Setup → Meas. mode → ORP
  • Unit: mV
  • Output: 4mA=-1000mV, 20mA=+1000mV
  • Damping: 2-5s
  • Temp. comp.: OFF

Two-Point Calibration:

  • Rinse electrode with DI water → Dry
  • CAL → Password 22 → ORP Cal
  • Point 1: +220mV standard → Stable → CAL
  • Rinse dry → Point 2: +468mV → Stable → CAL → Cal OK

No standards? Use Manual mode to enter mV value

Maintenance: Monthly water rinse, quarterly calibration, ensure 3mol/L KCl fill solution

11. CUE21 Online Turbidity

Application: 90° IR scatter with ultrasonic auto-clean

Parameters:

  • Unit: NTU
  • Range: Clean water 0-100 NTU
  • Filter time: 5-10 seconds
  • Ultrasonic cleaning: ON, cycle 15-30min, duration 10-20s

Two-Point Calibration:

  • Zero: 0 NTU ultrapure water → CAL → Zero cal → 2min → Drift <±0.02 NTU
  • Span: 10 NTU or 100 NTU standard → CAL → Span cal → Error <±1%

Return to AUTO mode when complete

12. CA80COD Online COD Analyzer

Application: Dichromate method, CM44x + reaction cabinet

Startup Self-Test: Confirm 220V AC and reagents (R1 potassium dichromate, R2 silver sulfate/sulfuric acid, R3 mercury sulfate) level >1/2 → Power on → ~20min self-test

Errors: E01=No sample (check filter/pump); E02=Reagent missing

Settings:

  • Range: 0-500 mg/L
  • Cycle: 30 min
  • Digestion: 165°C, 15 min
  • Output: 4-20mA=0-500 mg/L
  • Auto-clean: Every 24 hours
  • Auto-cal: Every 7 days

Two-Point Calibration: Prepare ultrapure (blank), 100mg/L low, 500mg/L high standards

  • Blank cal: Absorbance <0.02
  • Low+High cal: R²≥0.999
  • Check: 250mg/L standard, error ±10%

Maintenance Schedule:

  • Daily: Check reagent levels and tubing
  • Weekly: Blank cal + clean filter
  • Monthly: Two-point cal + replace pump tubing
  • Quarterly: Clean digestion cell/cuvette + replace all reagents

IV. Signal Conversion

13. RTA421 Relay / Signal Converter

Application: 4-20mA/0-10V to relay switch alarm output

Wiring:

  • L/N: 220V AC power
  • +IN/-IN: Field instrument signal input
  • +OUT/-OUT: 24V DC loop power (for sensor)
  • RL1/RL2: Two relay outputs (SPDT)

Quick Setup: Long press E 3s → Basic menu

  • Input Type: 4-20mA or 0-10V
  • Range: Match sensor (e.g., 0-1000 kg/h)
  • Display: PV

Alarm Settings:

  • AL1 High: Set Point (e.g., 800), Hysteresis 5% (50), Action NO/NC
  • AL2 Low: Low value (e.g., 200), Hysteresis 5%

Test & Save: Menu → Test → Relay → Trigger RL1/RL2 listen for “click” → Long press E → SAVE? → YES

Instrument Selection Quick Reference

Instrument Principle 가장 적합한 대상
72F Vortex + T/P compensation Saturated/superheated steam, general gases
PROMASS 80F Coriolis High-precision mass flow, custody transfer
DTT31 Thermal dispersion Low flow liquids, cooling water, lube oil
FMM50 Plumb bob mechanical Large solids silos, high dust
FMU23X Ultrasonic Standard open tanks, no vapor level
FMR245 26GHz radar Agitated, high temp, steam, dust tanks