I. Flow Measurement Instruments

1. PROMAG50 Electromagnetic Flowmeter

Application: Conductive liquid flow measurement

Pre-power Check:

  • Sensor full pipe, horizontal or vertical installation (flow upward)
  • Straight pipe runs: upstream 5D, downstream 3D
  • Lining intact, electrodes clean
  • Separate reliable grounding, resistance <10Ω

Quick Setup: Press E → QUICK SETUP → Password 50

  • Unit: m³/h
  • Range: 4mA=0, 20mA=full scale
  • Damping: 2-5s
  • Pipe diameter DN: per nameplate
  • Low flow cutoff: 0.5%-1% of range
  • Empty pipe detection: ON

Press +/- together for 3s to return

Zero Calibration: Full pipe, static, no flow → Menu → Calibration → Zero Adjust → Press E → Wait 10s → Zero OK (Normal: ±0.01 m³/h)

Current Check: 0%=4mA, 50%=12mA, 100%=20mA

2. PROMASS 80F Coriolis Flowmeter

Application: High-precision mass flow, density, temperature

Pre-power Check: Full pipe, no bubbles, no vibration; avoid strong magnetic fields and >200°C; flange seals intact; housing grounded

Basic Setup:

  • Setup → Unit → Mass flow: kg/h
  • Range: 4mA=0, 20mA=full scale
  • Damping: 2-5s
  • Fluid: Liquid/Gas
  • Measuring mode: Standard/Symmetry

Zero Calibration: Full pipe, no flow, static → Menu → Calibration → Zero adjust → Press E → Wait 30s → Complete. NEVER calibrate with empty pipe!

Empty Pipe Detection: Menu → Setup → Empty pipe → ON, threshold default 5%

3. 72F Vortex Flowmeter

Application: Steam, gas, liquid flow measurement

Installation: Upstream ≥10D, downstream ≥5D straight runs; arrow matches flow direction; horizontal pipes level, vertical pipes bottom-to-top; away from pumps/compressors

Wiring: 24V DC, 4-20mA+HART

Quick Commissioning: Long press E 3s → Basic menu

  • Set Tag and medium type (Steam/Gas/Liquid)
  • Unit: Steam=kg/h, Gas=Nm³/h, Liquid=m³/h
  • Enter Range span
  • Select Diameter (e.g., DN50)

Mass Flow Calculation:

  • Temp: Select Internal (built-in sensor)
  • Pressure: External if transmitter connected, else fixed working pressure

Zero Calibration: Full pipe, no flow, temp stable → Menu → Cal → Zero Cal → Wait 60s → OK. Output → LFC set 2%-5% low flow cutoff

Errors: A001=Vibration (reinforce piping); A002=Low flow (check cutoff or valve)

4. DTT31 Thermal Mass Flowmeter

Application: Cooling water, lubricating oil low flow monitoring

Installation: Full pipe; 5D upstream straight run; sensor fully immersed, tip at pipe center, insertion ≥10mm; horizontal=side mount, vertical=bottom-to-top

Display: White=normal, Red=alarm

Wiring: 24V DC, output 4-20mA + 1-2 switch outputs

Commissioning: Long press E 3s → Basic menu → Set unit (kg/h or m³/h), range, output mode

Two-Point Calibration:

  • Learn Low (0%): Stop pump, zero flow → Press E → 30s → OK
  • Learn High (100%): Max stable flow → Press E → 30s → OK
  • Select YES when prompted SAVE?

Faults: W432=Unstable calibration retry; Flow drift → Set Temp Comp ON

II. Level & Pressure Instruments

5. FMR245 Radar Level Transmitter

Application: Non-contact liquid, slurry, solids (26GHz)

Installation: ≥300mm from tank wall, avoid inlets/agitators; antenna perpendicular to surface; nozzle height ≤150mm, ID ≥100mm

Quick Setup: Long press E 3s → Basic Setup

  • Language: Select
  • Tank Shape: Vertical/Horizontal/Sphere
  • Medium: Liquid/Solid
  • Empty Cal (0%): Distance D from flange to lowest level
  • Full Cal (100%): Distance L from flange to highest level

Echo Optimization: Menu → Envelope → Auto Learn → Auto scan 30s (filters interference)

أمان: Safety menu set SD safety distance (e.g., 0.2m)

Test: Output → Test → Manual output 4mA/12mA/20mA to verify DCS

6. FMU23X Ultrasonic Level Transmitter

Application: Standard liquid and solids level

Installation: Probe parallel to surface; ≥30cm from tank wall; off-center from tank top; avoid inlets/obstacles

Factory Reset: Press V+H together → Display V9H5 → Change to 333 → Press H

معايرة:

  • Empty: V0H1 → Enter sensor to zero distance → Press H
  • Full: V0H2 → Enter zero to full scale distance → Press H

Fault Check: Err displayed → Enter V9H0 for error code

7. FMM50 Plumb Bob Level Sensor

Application: Large solids silos mechanical measurement

Commissioning:

  • Basic setup → Empty: Flange to reference zero distance
  • Block distance: Flange to weight end safety distance
  • Full: 20mA corresponding max level distance
  • Mode: Periodical (cyclic measurement)
  • Time interval: Set cycle
  • Current output → Standard → 4-20mA
  • Linearization → Level DU → Linear → Unit m

Press +/- together to return

8. PMP71 Pressure Transmitter

Application: High-precision pressure measurement

Local Setup: Long press E 2s → Setup

  • Unit: bar/MPa/kPa
  • Measuring range: LRV lower, URV upper
  • Damping: 2-5s

Position Zero: Zero pressure, drain valve open, membrane vented → Setup → Pos. zero adjust → Confirm → Adjustment OK (Output 4.000mA)

HART Communicator:

  • Connect across signal lines → Auto-detect PMP71
  • Verify Tag and range
  • Device Setup → Calibration → Zero Trim
  • With pressure source: 100% pressure → Span Trim enter standard
  • Check 50% point: Should be 12.000mA (±0.02mA)

III. Water Quality Analyzers

9. COM223/COM253 Dissolved Oxygen

Application: Wastewater and industrial water monitoring

Air Calibration: Install membrane with electrolyte → Expose to air (avoid sun, 20-25°C) → Connect transmitter → Press CAL → Password 22 → Air cal → E confirm → Value drops 600 to 0 → No error = complete

Normal Range:

  • Altitude mode: 6.00-11.20mg/l or 85%-157%SAT
  • Salinity mode: 9.20-9.30mg/l or 102%SAT

Settings:

  • Unit: E → Password 22 → Setup1 → Unit → mg/L
  • Current output: E → Password 22 → — → Output → 4-20mA → Enter concentration values

Maintenance: Weekly water rinse; Industrial wastewater (H₂S, ammonia, etc.) requires more frequent cleaning/membrane replacement

10. CPM223/CPM253 ORP Analyzer

Application: جهد الأكسدة والاختزال

إعداد بدء التشغيل: (قد يتم ضبط القيمة الافتراضية على درجة الحموضة، قم بتغييرها فوراً)

  • الإعداد ← وضع القياس ← جهد الاستجابة الكهروكيميائية
  • الوحدة: ملي فولت
  • الناتج: 4 مللي أمبير = -1000 مللي فولت، 20 مللي أمبير = +1000 مللي فولت
  • Damping: 2-5s
  • تعويض درجة الحرارة: إيقاف

Two-Point Calibration:

  • اشطف القطب الكهربائي بالماء منزوع الأيونات ← جففه
  • كال → كلمة المرور 22 → أورب كال
  • النقطة 1: +220 مللي فولت قياسي ← مستقر ← معايرة
  • اشطف وجفف → النقطة 2: +468 مللي فولت → مستقر → معايرة → معايرة جيدة

لا توجد معايير؟ استخدم الوضع اليدوي لإدخال قيمة mV

Maintenance: شطف بالماء شهريًا، ومعايرة ربع سنوية، والتأكد من استخدام محلول تعبئة بتركيز 3 مول/لتر من كلوريد البوتاسيوم.

11. عكارة CUE21 عبر الإنترنت

Application: تشتت الأشعة تحت الحمراء بزاوية 90 درجة مع التنظيف التلقائي بالموجات فوق الصوتية

حدود:

  • الوحدة: NTU
  • النطاق: مياه نظيفة 0-100 وحدة عكارة نفيلومترية
  • مدة الترشيح: 5-10 ثوانٍ
  • التنظيف بالموجات فوق الصوتية: تشغيل، دورة من 15 إلى 30 دقيقة، مدة من 10 إلى 20 ثانية

Two-Point Calibration:

  • صفر: ماء فائق النقاء 0 NTU ← معايرة ← صفر معايرة ← دقيقتان ← انحراف <±0.02 NTU
  • المدى: 10 NTU أو 100 NTU قياسي ← معايرة ← معايرة المدى ← الخطأ <±1%

العودة إلى الوضع التلقائي عند الانتهاء

12. محلل الطلب الكيميائي للأكسجين عبر الإنترنت CA80COD

Application: طريقة ثنائي الكرومات، CM44x + خزانة التفاعل

اختبار ذاتي للشركات الناشئة: تأكد من أن جهد التيار المتردد 220 فولت ومستوى الكواشف (R1 ثنائي كرومات البوتاسيوم، R2 كبريتات الفضة/حمض الكبريتيك، R3 كبريتات الزئبق) أكبر من النصف ← تشغيل الجهاز ← اختبار ذاتي لمدة 20 دقيقة تقريبًا

Errors: E01=لا توجد عينة (تحقق من الفلتر/المضخة)؛ E02=الكاشف مفقود

Settings:

  • النطاق: 0-500 ملغم/لتر
  • مدة الدورة: 30 دقيقة
  • الهضم: 165 درجة مئوية، 15 دقيقة
  • الناتج: 4-20 مللي أمبير = 0-500 ملغم/لتر
  • التنظيف التلقائي: كل 24 ساعة
  • المعايرة التلقائية: كل 7 أيام

Two-Point Calibration: حضّر محاليل قياسية فائقة النقاء (خالية من المادة)، ومحاليل قياسية منخفضة التركيز (100 ملغم/لتر)، ومحاليل قياسية عالية التركيز (500 ملغم/لتر).

  • معايرة فارغة: الامتصاص <0.02
  • سعرات حرارية منخفضة + عالية: R²≥0.999
  • التحقق: معيار 250 ملغم/لتر، خطأ ±10%

جدول الصيانة:

  • يومياً: تحقق من مستويات الكواشف والأنابيب
  • أسبوعيًا: سعرات حرارية فارغة + فلتر نظيف
  • شهرياً: معايرة نقطتين + استبدال أنابيب المضخة
  • ربع سنوي: تنظيف خلية الهضم/الكوفيت + استبدال جميع الكواشف

رابعاً: تحويل الإشارة

13. مرحل/محول إشارة RTA421

Application: 4-20 مللي أمبير / 0-10 فولت إلى مخرج إنذار مفتاح الترحيل

Wiring:

  • L/N: طاقة تيار متردد 220 فولت
  • +IN/-IN: مدخل إشارة جهاز ميداني
  • +OUT/-OUT: طاقة حلقة تيار مستمر 24 فولت (للمستشعر)
  • RL1/RL2: مخرجان مرحليان (SPDT)

Quick Setup: Long press E 3s → Basic menu

  • نوع الإدخال: 4-20 مللي أمبير أو 0-10 فولت
  • المدى: مطابقة المستشعر (على سبيل المثال، 0-1000 كجم/ساعة)
  • شاشة العرض: PV

إعدادات المنبه:

  • AL1 عالي: نقطة الضبط (مثلاً، 800)، التباطؤ 5% (50)، الإجراء NO/NC
  • AL2 منخفض: قيمة منخفضة (مثلاً، 200)، التخلف 5%

اختبر واحفظ: القائمة ← اختبار ← مرحل ← تشغيل RL1/RL2 استمع لصوت "نقرة" ← اضغط مطولاً على E ← حفظ؟ ← نعم

دليل سريع لاختيار الأدوات

أداة مبدأ الأفضل لـ
72 فهرنهايت تعويض الدوامة + T/P البخار المشبع/المحمص، الغازات العامة
بروماس 80 فهرنهايت كوريوليس تدفق الكتلة عالي الدقة، ونقل الملكية
DTT31 التشتت الحراري سوائل منخفضة التدفق، ماء التبريد، زيت التشحيم
FMM50 خيط ميزان ميكانيكي صوامع كبيرة للمواد الصلبة، غبار كثيف
FMU23X الموجات فوق الصوتية خزانات مفتوحة قياسية، بدون مستوى بخار
FMR245 رادار بتردد 26 جيجاهرتز خزانات غبار ذات درجة حرارة عالية ومُحَرَّكة وبخار

احصل على عرض سعر

العلامات التجارية المتوفرة

انتقل إلى الأعلى