Accuracy
Classic: +0.065% of span, For spans less than 10:1: ±[0.015 + 0.005(URL / Span)]% of span
Ultra: +0.055% of span, For spans less than 10:1: ±[0.015 + 0.005(URL / Span)]% of span
Output
Two-wire 4-20 mA is user-selectable for linear or square root output. Digital signal based on HART Protocol.
Range
0-8.3 in H2O to 0-300 psi
Power
3051S with Advanced HART Diagnostic Suite: 12-42.4 V dc with no load
Material
316L SST, Alloy C-276, Alloy 400, Tantalum, Gold-plated Alloy 400, Gold-plated 316L SST, see full specs for complete list of materials
Mounting
Flanged: ANSI/ASME, EN/DIN, GOST, & JIS
�Threaded: NPT, DIN, ISO
�Hygienic