핵심적인 기술적 이점
-
Flexible Application Range: The PMD55 is a “3-in-1” solution. It can be configured for level measurement (volume or mass), differential pressure monitoring (across filters or pumps), and flow measurement (when used with an orifice plate or Pitot tube).
-
Electric HP/LP Switch: A standout feature is the internal electric switch on the electronics. This allows you to swap the high-pressure (HP) and low-pressure (LP) sides without physically re-plumbing the impulse lines, significantly simplifying onsite installation errors.
-
SIL2 Safety by Design: Certified to IEC 61508 and IEC 61511, the PMD55 is ready for use in safety-instrumented systems (SIS), providing reliable monitoring for critical process pressures.
-
Modular and User-Friendly: The device features a modular concept where the display or electronics can be replaced easily in the field. The menu-guided Quick Setup allows for fast commissioning, reducing the technical expertise required for initial configuration.
-
High Precision Options: While the standard accuracy is ±0.1%, a “Platinum” version is available that provides an accuracy of ±0.075%, ensuring precise data for critical mass flow or inventory calculations.
-
Broad Integration: It supports all major industrial communication protocols, including 4-20mA HART, PROFIBUS PA, and FOUNDATION Fieldbus, allowing it to fit into almost any existing control architecture.
기술 성능 매트릭스
| 기능 | 세부 정보 |
| 측정 원리 | 차압(압전저항) |
| 센서 유형 | 용접 금속막 |
| 정확성 | ±0.1% (표준) / ±0.075% (플래티넘) |
| 측정 범위 | 0.5 mbar to 40 bar (0.0072 to 600 psi) |
| 공정 온도 | -40~85°C(-40~185°F) |
| 안전 등급 | SIL2 (IEC 61508 / IEC 61511) |
| 커뮤니케이션 | HART, PROFIBUS PA, 파운데이션 필드버스 |
주요 응용 분야
-
Filter and Pump Monitoring: Detecting pressure drops across filters to schedule maintenance or monitoring pump performance to prevent cavitation and dry-running.
-
Flow Measurement: Calculating the volume or mass flow of steam, gases, and liquids in conjunction with primary elements like orifice plates or Venturi tubes.
-
Level in Pressurized Tanks: Measuring the hydrostatic head in closed vessels where the gas phase pressure must be subtracted to determine liquid height.
-
Steam Applications: Reliable monitoring of steam lines in power generation or industrial heating processes.
-
Environmental Monitoring: Tracking pressure differences in air filtration or scrubbing systems for emissions control.